PLAN REV 1.2MILESTONES 14COMPONENTS 26UPDATED 2026-11-17LICENSE CC BY-SA 4.0
C04.4 · Component of M04

HVDC grid and cable-laying rover

High-voltage DC cables, converters and switches that link the reactor, solar towers and storage to the habitat and oxygen plant. A small rover lays and covers the cable.
Sub-components · 6
1

Transmission cable

Carries power 1–3 km at high voltage so the conductor can be thin and light.

  • Aluminium conductor (≥16 AWG)
  • FEP insulation (design stress 4.4 kV/mm)
  • Outer FEP jacket
  • Vacuum-rated HV connectors and splices
  • Cable markers
BASIS: NASA GRC transmission studies; terrestrial HV cable practice · TRL 4
2

High-voltage converters

Step voltage up at each source and down at each user, using stacks of low-voltage switches.

  • Series-stacked DC–DC modules (175 V class switches)
  • High-frequency isolation transformers
  • Filter capacitors
  • Universal Modular Interface Converter (UMIC) to 120 VDC
  • AC–DC tie converter for an AC reactor interface
BASIS: NASA GRC ABSS converter (to 600 V); MIPS/UMIC · TRL 4
3

Switchgear and protection

Isolates faults quickly so one bad cable or load cannot drop the whole grid.

  • Solid-state DC circuit breakers
  • Mechanical disconnects for maintenance
  • Current-limiting in converters
  • Insulation monitoring and grounding
  • Surge protection
BASIS: Ohio State T-Breaker / DC energy router (NASA LuSTR) · TRL 3
4

Microgrids and control

Runs habitat and ISRU as separate local grids that can share power over the trunk.

  • 120 VDC buses and power distribution units
  • Regional grid controller
  • Local microgrid controllers
  • Priority load-shedding tables
  • Earth link for remote operation
BASIS: NASA Artemis Base Camp microgrid studies; Autonomous Power Control project · TRL 5
5

Cable-laying rover

Carries a cable reel from the lander, unreels it along a surveyed route and covers it.

  • Rover chassis and drive
  • Powered reel with tension control
  • Cable guide and payout counter
  • Shallow plough or regolith cover blade
  • Route cameras and lidar
BASIS: Astrobotic LunaGrid-Lite CubeRover and cable deployer · TRL 5
6

Fault location and monitoring

Finds and locates cable faults without sending a rover to walk the whole line.

  • Time-domain reflectometer at each node
  • Insulation resistance monitor
  • Partial-discharge sensors
  • Current and voltage sensors
  • Fault log to the grid controller
BASIS: Terrestrial TDR practice, to be adapted for lunar use · TRL 4
Engineering notes

What it does

The grid moves power from where it is made to where it is used. The reactor sits 1–3 km from users1, and the oxygen plant needs power over 3–5 km3. NASA’s baseline is two independent microgrids, one for the habitat and one for ISRU, each with its own sources. A primary line lets them share power3.

How it works

  • Why high voltage. At fixed efficiency, conductor mass falls with the square of voltage until insulation mass takes over1. For a 40 kW, 3 km, 95% efficient aluminium DC cable, the lightest point is about ±4,000 VDC1. The same 3 km cable weighs 3,300 kg at 500 V but 240 kg at 2,800 V2. A DC cable is a little lighter than an AC cable at the same rating1.
  • Cable. NASA assumed FEP insulation at 4.4 kV/mm (5 times the minimum breakdown thickness), a 0.6 mm FEP jacket, and conductors no thinner than 16 AWG. The design had no micrometeoroid shielding1.
  • Converters. Fully space-qualified silicon switches are limited to 160 V, so DC step-up needs stacked modules1. NASA’s series-stacked step-down converter has run up to 600 V1. A DC link needs about 4 times as many parts as an AC link1. In NASA’s 40 kWe concept, the step-down converter was 96.1% efficient and the distribution unit 98.4%. It fed eight 5 kWe outputs at 120 VDC2. Sources will not all speak the same language. The US reactor draft asks for a 3 kV AC interface at 1 km7, and Astrobotic proposed high-voltage AC for its towers10. Open Moon therefore puts a tie converter at every source. NASA’s UMIC is a bidirectional, modular converter that joins 120 VDC microgrids to the transmission line3.
  • Protection. DC breakers must put out an arc, because DC current never passes through zero; high-voltage DC breakers are still being researched1. Ohio State is building a modular “T-Breaker” DC energy router for lunar microgrids under NASA funding3.
  • Control. Each microgrid controls its own power. A regional controller makes power go to the highest-priority loads, such as the crewed habitat3.
  • Cable laying. Astrobotic’s LunaGrid-Lite pairs a 4U CubeRover with a robotic cable deployer. It is planned to carry 1 kW over 500 m of abrasion-resistant cable, with a high-voltage converter co-designed by NASA Glenn5. Earlier plans said 1 km, at a target of 1 kV and 1 kHz AC6. Open Moon needs a larger rover of the same kind for heavier ±4 kV cable.
  • Fault location. A time-domain reflectometer sends a pulse down the line and times the echo from any impedance change. An open circuit echoes with the same polarity and a short with the opposite polarity8.

Sizing

One 40 kW, 3 km link (this plan’s arithmetic):

Quantity Working Result
Current at ±4 kV 40 kW ÷ 8 kV 5 A
Allowed loss (95%) 5% × 40 kW 2 kW (0.7 W/m1)
Loop resistance 2,000 W ÷ 5² 80 Ω over 6 km = 13.3 Ω/km
Aluminium area 26.5 nΩ·m9 ÷ 0.0133 Ω/m ~2.0 mm²
Aluminium mass 2.0 mm² × 6 km × 2,699 kg/m³9 ~32 kg
Whole cable incl. insulation NASA, 2,800 V case2 ~240 kg
Same power at 120 V 40 kW ÷ 120 V 333 A (impractical)

Insulation, not metal, dominates cable mass at these voltages.

  • Reel mass (ESTIMATE). NASA’s 1 km cable plus spool was 325 kg in its 3 kV AC reference4. A 1 km ±4 kV reel of about 0.3–0.4 t is a fair planning figure, so the rover lays 3 km in three trips.
  • Fault location (ESTIMATE). With signal speed about 66% of light speed8, a 1 µs echo means a fault about 100 m away. 10 ns timing locates it to about 1 m.

Testing and qualification

  1. Cable samples. Run partial-discharge and breakdown tests in vacuum at −173 to +130 °C (the lunar range3), with dust. Then flex and abrasion tests.
  2. Converter stack. Raise the stacked converter from 600 V to ±4 kV in steps. Irradiate the parts for single-event effects.
  3. Hardware-in-the-loop microgrid. Connect real converters to simulated sources and loads. Inject faults and check that only the faulted section trips.
  4. Rover field trials. Lay and recover 1 km of cable on simulant slopes. Measure tension, payout accuracy and cover depth.
  5. On the Moon. Use LunaGrid-Lite’s flight results5 to set the first route. Energise each link at low voltage first, then at full voltage. Map its TDR signature as a baseline.

Open questions

  • DC or AC trunk? NASA studies call the masses comparable, but AC needs fewer parts14.
  • How deep must cable be buried to survive heat, micrometeoroids and rover traffic?
  • Can one standard tie converter serve the reactor, solar towers, storage and users?
  • Which lunar-qualified DC breaker design will be ready first?
  • Can aluminium cable later be made on the Moon (M12)?
Problems and solutions · 7
SeverityProblemSolution
CriticalRadiation-hard switches are rated only ~120–160 V, far below ±4 kV, and DC breakers for space are still research.Use series-stacked modules of flight-rated switches; keep AC transmission with transformers as a fallback; let trunk voltage be chosen per link.
HighSources may arrive with different interfaces: the reactor draft asks for 3 kV AC, and LunaGrid targets 1 kV AC.Put a standard tie converter (UMIC class) at every source and user, so the trunk standard is fixed in one place.
HighHigh voltage in vacuum risks partial discharge and arcing, made worse by abrasive dust on insulation.Use a 5× insulation margin, sealed connectors, and partial-discharge testing in vacuum with dust before flight.
HighCables on the surface can be damaged by rovers, thermal cycling and micrometeoroids; NASA's sizing had no impact shielding or redundancy.Cover or bury cables; mark crossings; build a ring so every node has two paths.
MediumLaying long cables on rough terrain can snag or overstress the cable; LunaGrid-Lite's demo length dropped from 1 km to 500 m.Survey routes from orbit and by rover first; use 1 km reels with field splices; monitor tension and payout.
MediumDC faults are hard to interrupt because current never passes through zero.Converters limit fault current within microseconds; solid-state breakers open the faulted section; mechanical switches isolate it after.
MediumSunlit cables run hot, raising aluminium resistance and losses.Cover cables with regolith; size for the hot case; monitor line losses.

Specification

Trunk voltage±4 kVDC (8 kV pole to pole)
User voltage120 VDC microgrids
ConductorAluminium, FEP insulation, vacuum rated
Trunk length1–3 km per link; ≥3 km laid in M04
Cable efficiency95% at 3 km, 40 kW
Cable mass~240 kg per 3 km, 40 kW link (NASA-derived)
ConvertersModular DC–DC, ~96% each; ~78% Stirling-to-user end to end
Microgrids2 (habitat, ISRU) plus source nodes
Rover1 cable layer, ~0.4 t reel per trip (ESTIMATE)
Fault locationTime-domain reflectometry from each node
Technology readiness · TRL 4 / 9

Sources

  1. Barth & Pike, NASA GRC: Lunar power transmission for fission surface power (2022)
  2. Oleson et al., NASA GRC: A Deployable 40 kWe Lunar Fission Surface Power Concept (NETS 2022) (May 2022)
  3. Csank & Scott, NASA GRC: Power and Energy for the Lunar Surface (Apr 2022)
  4. INL/NASA: Fission Surface Power Technical Maturation Webinar (Sep 2025)
  5. Astrobotic: LunaGrid-Lite completes critical design review (2025)
  6. SatNews: Astrobotic's LunaGrid VSAT enters thermal vacuum testing (press) (Jul 2024)
  7. NewSpace Economy: What NASA's SPARC procurement reveals about Lunar Reactor-1 (secondary) (Sep 2026)
  8. Wikipedia: Time-domain reflectometer (2026)
  9. Wikipedia: Aluminium (2026)
  10. NASA GCD: Vertical Solar Array Technology project annual review (Sep 2023)
ProjectOPEN MOON · Self-sustaining lunar colony
DocumentC04.4
Revision1.2 · Draft
EditEdit on GitHub